The Zenitel intercom integration allows the local workstation to interact with any intercom that supports the IC-Edge Driver.
Access It! Universal.NET Licensing
The following licensing option must be enabled within the Access It! Universal.NET dongle and is a per client license.
- Intercom Integration - 1/x
- DVR Integration - 1/x
Only required when using using video enabled intercoms.
While DVR Integration licensing is utilized, there is no video recording.
- Up to 64 total Zenitel IP devices
- Up to 10 VS Clients (PC clients)
- Up to 10 third party SIP devices
- Up to 10 Zenitel mobile clients
- Up to 10 telephone gateways are supported
- Up to 50 IC-Edge systems can be networked together
Additional Zenitel Licencing may be needed. Please contact Zenitel for more information.
Here is a full list of IC-Edge Supported Devices.
Enable Intercom Integration
This is enabled on a per workstation basis.
- Click File
- Click Workstation Settings...
- Select the Integration tab
- Select the Enable intercom Integration checkbox
- Select the intercom/handset device as the Associated Intercom Station
- Check the Auto Connect on Intercom Select checkbox
- Click Save
Adding The Intercom Controller
- Navigate to the hardware tree from the navigation pane
- Click Intercom Controllers
- Click New
- Enter the name for the Intercom controller
- Select the Intercom controller type Zenitel IC-EDGE Driver
- Enter the IP Address
- Enter the Port number
The default port number is 50004. - Click Save
Adding Intercom Stations
- Select the Intercom Controller
- Click New on the Stations tab
- Enter Station Name
- Enter Station ID
- Click Save
- Restart the workstation
Video enabled intercoms require the Zenitel Video Intercom Viewer File.
Enable DVR Integration
While the Zenitel integration is using the DVR section there is no recorded video.
This is enabled on a per workstation basis.
- Click File
- Click Workstation Settings...
- Select the Integration tab
- Select the Enable DVR Integration checkbox
- Click Save
- Restart the workstation
Adding Video Intercoms
Each video intercom must be added as a new video recorder
- Navigate to the hardware tree from the navigation pane
- Click Video Recorders
- Click New
- Click Other...
- Navigate to the Zenitel Video Intercom Viewer File
- Click Open
- Select Zenitel Video Intercom
- Click Ok
- Enter the name for the Intercom controller
- Enter the Viewer URL
- Click Save
Adding Video Intercom Cameras
- Click New on the Cameras tab
- Enter a camera name
- Leave Camera ID blank
- Click Save
When using the Zenitel IC-EDGE driver, a macro can be associated to a specific reader to unlock the door from the handset by pressing the number '6' and then hanging up the handset.
Unlock Door Command from Zenitel Handset
- Navigate to Main
- Select Macros
- Select New Macro
- Name the Macro appropriately
- Click Next
- Select Grant Access command and add the specific reader to grant access to
- Click Finish
- Navigate to Hardware
- Select Intercom Controllers
- Edit the Intercom Station at the respective reader
- Select the Events tab
- Associate the Grant Access Macro under the Door Open Request Macro drop-down
- Click Save
The Zenitel Video Intercom Viewer file can be found in the Downloads section of the Dealer Area on the RS2 website.
Intercom Integration Resources | Zenitel Video Intercom Viewer File
End Users must contact their Authorized RS2 Dealer to obtain the downloadable Zenitel Video Intercom file.