Updating SCP Firmware Using the Panel Utility


Overview

If it is determined that the firmware of an SCP requires an upgrade, the Panel Utility may be used to update the firmware of a single board at a time.

Disable the Channel within Access It! Universal.NET

  1. Launch Access It! Universal.NET
  2. Navigate to Hardware | Channels in the Navigation pane on the left hand side of the screen
  3. Edit the Channel associated with the SCP to be upgraded
  4. Uncheck Channel Enabled
  5. Click Save

Updating SCP Firmware

  1. Navigate to and launch the Panel Utility (Start | All Programs | Access It! Universal.NET | Client Utilities | Panel Utility)
  2. Click Attach, and enter the proper Panel Type, Comm Type, Address, IP Address, and TCP Port
  3. If the panel is properly connected, there will be a green Online in the lower right hand corner
  4. Once connected, select Download SCP Firmware from the ribbon
  5. Navigate to the desired firmware, and open the appropriate firmware for the board
  6. The panel will cycle between online and offline within the Panel Utility. Once the board stabilizes with the proper firmware reflected at the bottom of the pane, the panel should be finished downloading firmware.
  7. Detach the SCP from the Panel Utility

Enable the Channel with Access It! Universal.NET

  1. Launch Access It! Universal.NET
  2. Navigate to Hardware | Channels in the Navigation pane on the left hand side of the screen
  3. Edit the Channel associated with the SCP that has been upgraded
  4. Check Channel Enabled
  5. Click Save

  • 759
  • 28-Mar-2019
  • 140 Views