SCP incorrectly displays Normal/Encrypted

Symptoms
SCP incorrectly displays Normal/Encrypted instead of Normal.

Cause
The SCP is running with dip switch 2 set to the ON position. (Normal operation is ALL dip switches set to the OFF position, except for LP series panels running in legacy mode, wherein dip switch 4 is set to ON).

Resolution
Remove power from the panel, turn dip switch 2 to the off position, and restore power.