Configuring Universal To Utilize The Casi Proximity Readers


Overview

This document outlines the steps required to use Casi F/2F proximity readers with Access It! Universal.
If using a Series I MR-50 or MR-52 panel, the SIO must be at revision 13 or higher.

Reader Settings
If using the GE 94x or 97x it must be configured to use F/2F operating mode (Switch 5 ON, Switch 6 OFF).
Refer to the readers installation manual for additional information about configuring the reader.

Access It! Universal Setup

  1. From the File menu, select Go | System | Sites
  2. Edit the site the Casi reader will be installed under
  3. Select Card Options
  4. Enable Use Large Card Number
  5. Click Save
    All SCPs within the site will reset.
  6. Log Out of Access It! Universal
  7. Log into Access It! Universal
  8. From the File menu, select Go | Main | Hardware
  9. Select Installed Readers from the left hand menu
  10. Edit the Casi reader
  11. Select the Reader Settings tab
  12. Set Reader Type to Case Proximity F/2F
  13. Click Save
  14. Select SCPs from the left hand menu
  15. Edit the SCP the Casi reader is installed under
  16. Select Card Formats
  17. Select Edit Card Formats
  18. Select New
  19. Name the format 12 Digit Magstripe Casi F/2F
  20. Set the card format as outline in the 12 Digit Magstripe Casi F/2F Card Format article
  21. Click OK
  22. Click Save
  23. Select the newly created format
  24. Assign a Facility code of -1
  25. Click Save
    The SCP will reset.

Casi F/2F Readers to EP-1502 / MR-52 Wiring

EP-1502 / MR-52

GE 940

GND

PIN 4

Data 0

PIN 3

CLK 

PIN 2

BZR 

N/A

LED 

N/A 

VO 

PIN 5

A jumper must be placed between CLK and BZR.

  • 62