Vanderbilt Integration


Overview

Access It! Universal 5.3 adds support for the Mercury EP controllers to communicate downstream to Vanderbilt sub panels. Currently the Vanderbilt VRINX and VIONX-8 panels are supported. 

Additional Notes

  • Support was added for the Vanderbilt GIONX24 as of firmware version 1.23.6
    As of 5/04/2018, this model has not been tested by RS2 Technologies due to lack of availability.
  • Card Or PIN mode is not supported.
  • MR10/20 reade tamper is not supported.
  • REX must be wired and configured as a normally open circuit.
  • Door will be unlocked as long as REX input is in a closed state. REX timer begins upon initial change of state to the open state
  • Custom LED behavior is not supported.
  • Vanderbilt hardware must be communicating using the G-Protocol
  • The SCHLAGE Bright Blue hardware is not supported

Access It! Universal.NET Licensing
The following licensing option must be enabled within the Access It! Universal.NET dongle and is a per integrated reader count license.

  • Integrated Reader Count - 1/x

Installation Requirements

The Vanderbilt integration requires the following:

  • Access It! Universal.NET min s/w v5.3
  • Access It! Universal.NET optional Integrated Reader Count license enabled for the number of readers running on the system
  • EP-2500 and EP-4502 Series Controllers min f/w 1.212

Physical Addressing

A total of 16 Vanderbilt SIO modules may be connected to an EP controller. The physical address of each SIO board must be unique and can be configured as detailed in the following table. Notice that the Access It! Universal.NET addresses range between 0 through 15 while the Vanderbilt addresses range from 1 through 16.

Reference jumper block W10 for VRINX Reader Interfaces and W3 for VIONX-8 Input/Output boards.

WARNING! - When configuring the software, be sure to use the CORRECT Access It! Universal.NET SIO address associated to the Vanderbilt physical address. Failure to do so will result in the EP controller continuously rebooting.

Access It! Universal.NET
SIO Address
Vanderbilt
Physical Address

Physical
Jumper Settings

0 1 1, 2, 4, 8
1 2 2, 4, 8
2 3 1, 4, 8
3 4 4, 8
4 5 1, 2, 8
5 6 2, 8
6 7 1, 8
7 8 8
8 9 1, 2, 4
9 10 2, 4
10 11 1, 4
11 12 4
12 13 1, 2
13 14 2
14 15 1
15 16 None

Configuring Access It! Universal.NET 5.3

  1. Install and configure the EP series controller within Access It! Universal
  2. From the file menu, select Main | Hardware
  3. Select SCP’s
  4. Edit the EP series controller
  5. Set the SIO Port Speed to 38400 for the port the Vanderbilt panels are attached to
  6. Set Protocol to Vanderbilt for the port the the Vanderbilt panels are attached to
  7. Click Save
    The EP controller board will reset.
  8. From the left hand tree, expand SCP’s
  9. Expand the EP series controller the Vanderbilt panels are attached to
  10. Select SIOs
  11. From the right hand pane, edit the SIO whose address matches the configured address
  12. Enter a name for the Vanderbilt panel within the SIO Name field
  13. Set Model to the corresponding Vanderbilt panel
  14. Check Device Installed
  15. Set Channel accordingly
  16. Click Save
  17. Repeat steps 10-16 for each additional Vanderbilt panel