Privacy Extended Feature


Overview

The Privacy Extended Feature allows for the ability to lock a reader when a custom defined interior push button changes state. The reader will return to its default mode when the push button reverses state, or a Request to Exit (REX) occurs from the secure side of the opening. When using an Allegion AD series locksets or ASSA ABLOY Aperio lockset, the privacy button is built into the reader.

The Privacy functionality operates during the Always Timezone and does not respect Card Groups. If this feature is needed to operate during a limited schedule, or respect Card Groups, separate Tasks should be created.

Implementation

Mercury Readers

EP Firmware 1.18X firmware required.

  1. Within Access It! Universal V7.x, navigate to the Hardware Tree (Go | Main | Hardware)
  2. Select Installed Readers
  3. Edit the Reader that will be using the Privacy Extended Feature
  4. Select the Extended Feature tab
  5. Select the Extended Feature Type Privacy
  6. Select the SIO the interior push button is attached to
  7. Select the input number the interior button is attached to
  8. Click Save

Allegion AD 300/400 Readers

  1. Within Access It! Universal V7.x, navigate to the Hardware Tree (Go | Main | Hardware)
  2. Select Installed Readers
  3. Edit the Reader that will be using the Privacy Extended Feature
  4. Select the Extended Feature tab
  5. Select the Extended Feature Type Privacy - Schlage 
  6. Click Save

ASSA ABLOY Aperio Readers

  1. Within Access It! Universal V7.x, navigate to the Hardware Tree (Go | Main | Hardware)
  2. Select Installed Readers
  3. Edit the Reader that will be using the Privacy Extended Feature
  4. Select the Extended Feature tab
  5. Select the Extended Feature Type Privacy 
  6. Click Save